4 current limitation controller (imax controller), Current limitation controller (imax controller), Configuration – Lenze 8200 Frequency inverters User Manual

Page 155: 4 current limitation controller (i, Controller), Only “hvac” controllers

Advertising
background image

Configuration

8200SHB0199

7-18

7.5.4

Current limitation controller (I

max

controller)

Only “HVAC” controllers

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C077* Gain (V

P

)

I

max

controller

0.25

0.00

{0.01}

1.00

C078* Integral action time

(T

i

)

I

max

controller

65

12

{1 ms}

9990

Function

For power control, the I

max

controller can be adjusted under C077 and C078.

The following values for V

P

and T

i

are internally set if C077 and C078 are factory set:

Control mode

I

max

controller works internally

with

Setting for

V

P

T

i

C077

C078

C014 = -2-, -3-

0.25

65 ms

0.25

65 ms

C014 = -4-

0.5

*

87 ms

*

0.25

65 ms

*

Internally converted with a factor

Adjustment

The I

max

controller is factory set to stability.

For power control of extreme masses set the following:

-

C014 = -2- or C014 = -3- (characteristic control)

-

V

P

and T

i

are to be rated as follows:

- C077 = 0.06
- C078 = 750 ms

Important

C077 and C078 are only stored in parameter set 1.