Configuration

8200SHB0199

7-16

7.5.2

Acceleration and deceleration times T

ir

, T

if

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C012 Acceleration time T

ir

820X

5.00

0.00

{0.05 s}

999.00

821X/822X/

824X

5.00

0.00

{0.02 s}

999.00

0.00

{0.02 s}

1300.00 HVAC only

C013 Deceleration time T

if

820X

5.00

0.00

{0.05 s}

999.00

821X/822X/

824X

5.00

0.00

{0.02 s}

999.00

0.00

{0.02 s}

1300.00 HVAC only

Function

The acceleration and deceleration times determine the controller response after a setpoint change.

Adjustment

-

The acceleration and deceleration times refer to a change of the field frequency from 0 Hz to the
max. field frequency set under C011.

-

Calculate the times T

ir

and T

if

, which must be set under C012 and C013.

- t

ir

and t

if

are the times desired for the change between f

d1

and f

d2

:

7

LU

W

LU

ô

I

GPD[

I

G

I

G

7

LI

W

LI

ô

I

GPD[

I

G

I

G

Important

Under unfavourable operating conditions, too short acceleration and deceleration times can lead to
the deactivation of the controller with the indication of TRIP OC5. In these cases, the acceleration
and deceleration times should be short enough that the drive can follow the speed profile without
reaching I

max

of the controller.

Special features

820X

The slope is adjustable between 0.095 Hz/s and 780 Hz/s.

f /Hz

d

f

dmax

d2

f

fd1

0

tir

tif

Tir

Tif

t