Configuration

8200SHB0199

7-19

7.5.5

Control mode

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C014

¤ Control mode

820X

-0-

-0-

Linear characteristic V

f

d

with

auto boost

-1-

Square characteristic V

f

d

2

with

auto boost

-2-

Linear characteristic V

f

d

with

constant V

min

boost

-3-

Square characteristic V

f

d

2

with

constant V

min

boost

821X/822X/

824X

-4-

-4-

Motor-current control

Function

Under C014 you can set the control mode and the voltage characteristic. It is also possible to adapt
your drive to different load characteristics:

-

Linear characteristic for drives with constantly increasing load torques in relation to the speed

-

Square-law characteristics for drives with a load torque squared in relation to the speed

Square-law V/f characteristics are mainly used for centrifugal pump and fan drives. It is however
necessary to check whether your individual pump or fan application can be driven with this control
mode.

-

If your pump or fan drive cannot be operated with a square-law V/f characteristic, you should
select the control mode C014 = -0-, -2- or -4-.

820X

V/f-characteristic control with auto boost
The control mode mentioned above enables low-loss operation of stand-alone drives with
three-phase AC standard asynchronous motors with load dependent V

min

boost.

C014 = -0-
Linear characteristic

C014 = -1-
Square characteristic
(e.g. for pumps, fans)

1 0 0 %

0

0

1

f d

f d r

V m i n

0

0

1

f d

f d r

V m i n

V o u t

1 0 0 %

V o u t

A u t o b o o s t

A u t o b o o s t