Installation

8200SHB0199

4-38

4.2.8

Control connections

4.2.8.1

Control cables

-

Connect the control cables to the screw terminals:

Max. permissible cable cross-section

Tightening torques

2.5 mm

2

0.5 ... 0.6 Nm (4.4 ... 5.3 lbin)

-

We recommend the unilateral screening of all cables for analog signals to
avoid signal distortion.

-

Connect the screens of the control cables
- 820X:

To the front FAST-ON connector

- 8211 - 8214:

To the front FAST-ON connector

- 8215 - 8218:

To the front metal surface (screw length max. 12 mm).

- 822X, 824X

With the screen sheet to the front
metal surface
(screw length max. 12 mm).

-

If the control cables are interrupted (terminal strips, relays), the screens
must be reconnected over the shortest possible distance.

-

Connect the fixing screw of the setpoint potentiometer to PE.

-

Motor-temperature monitoring
(Optionally for 820X/821X, as standard for 822X/824X)
- If possible, separate the cables from the motor cable.

4.2.8.2

Assignment of the control terminals

Protection against contact - 820X/821X

-

The control terminals have a basic isolation (single insulating distance).

-

If protection against contact is required,
- a double insulating distance must be provided,
- the components to be connected must have a second insulating distance.

Protection against contact - 822X/824X

-

The control terminals are separated (VDE 0160, EN50178), the protection
against contact is ensured without additional measures.