Commissioning, Stop, Code settings for unit 1 – Lenze 8200 Frequency inverters User Manual

Page 132: Procedure for setting skip frequencies

Advertising
background image

Commissioning

8200SHB0199

5-27

Application FIG 5-5:

The air conditioning system of a department store is to be controlled according to
the number of persons present. The fans must circulate an amount of air that
depends on the number of people (e.g. data provided by a person counter).

Functions used

-

Belt monitoring

-

Flying-restart circuit on coasting motor

-

Suppression of mechanical resonances

-

Smooth start and stop with S-ramps

Code settings for unit 1:

Code

Name

Possible settings

Code

Name

Lenze

Choice

Info

C001 Operating mode

-0-

-0-

Setpoint selection via term. 8 (jumper setting, se
chapter 4.2.8.2)
Control via terminals parameter setting with 8201BB

C005 Configuration

-0-

-0-

Operation with open-loop control via terminal 8

C008 Function relay K1

-1-

-14-

Apparent motor current (C054) < Current threshold
C156 and acceleration finished (Belt monitoring)

C014 Control mode

-0-

-3-

Square characteristic V

f

d

2

with constant V

min

boost

C142 Start condition

-1-

-3-

Automatic start, if term. 28 HIGH, flying-restart circuit
active

C156 Current threshold

0

50 %

C182 t

integration

RFG S-shape

0.00

0.50 s

Smooth start / stop

C625 Skip frequency 1

480.00

30.00 HzRemoval of mechanical resonances

C628 Skipping bandwidth, f

skip

0.00

10.00 %

Procedure for setting skip frequencies

Stop!

If the mechanical resonance points are approached, the mechanics may be
damaged.

1. Remain C625 to C628 in factory setting.

2. Detect mechanical resonances (if not already known).

3. Detect the bandwidth of the mechanical resonances.

4. Set C625 to C628 according to the data available.

Note!

Terminal E3 must always be at L level (PAR2: normal operation; PAR1: QSP).