Installation

8200SHB0199

4-29

Protection

Fuses and cable cross-sections

The specifications in chapter 3.6 are recommendations and refer to the application

-

in control cabinets and machines,

-

installation in the cable duct,

-

max. ambient temperature + 40

•C,

-

as single drive with matching motor.

Selection of the cable cross-section

For selection take into account the voltage drop when being loaded
(to DIN 18015 part 1:

3 %).

Protection of cables and controller on
the AC side (L1, L2, L3)

-

By standard commercial fuses.

-

Fuses in UL-conform plants must have UL approval.

-

The rated voltages of the fuses must be dimensioned according to the mains voltage
at the site. The activation characteristic is defined by ”H” or ”K5”.

Protection of cables and controller on
the DC side (+ U

G

, -U

G

)

-

By means of recommended DC fuses.

-

The fuses/fuse holders recommended by Lenze are all UL-approved.

For DC group drives or supply via DC
source

Observe notes in Part F.

Connection of a brake unit

If the unit is connected to the terminals + U

G

/ -U

G

, the fuses and cross-sections

indicated in chapter 3.6 are not valid. These unit-specific data can be obtained from the
technical documentation for the brake unit.

Further information

For protection of cables and controllers, see chapter ”Accessories”.

Further standards

The compliance with other standards (e.g. VDE 0113, VDE 0289, etc.) remains in the
responsibility of the user.

4.2.7.2

Motor connection

For EMC safety reasons we recommend the use of screened motor cables.

Note!

The screening of the motor cable is only required to comply with existing standards
(e.g. VDE 0160, EN 50178).

Screen connection

-

820X: On the front FAST-ON connector.

-

8211 - 8214: On the front FAST-ON connector.

-

8215 - 8218: On the front metal surface.