Commissioning – Lenze 8200 Frequency inverters User Manual

Page 109

Advertising
background image

Commissioning

8200SHB0199

5-4

5.3.2

Setting of acceleration and deceleration times (T

ir

, T

if

)

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C012 Acceleration time

Variant “Standard”

820X

5.00

0.00

{0.05 s}

999.00 T

ir

821X/822X/

824X

5.00

0.00

{0.02 s}

999.00

C013 Deceleration time

Variant “Standard”

820X

5.00

0.00

{0.05 s}

999.00 T

ir

821X/822X/

824X

5.00

0.00

{0.02 s}

999.00

C012 Acceleration time

5.00

0.00

{0.02 s}

1300.00 T

ir

Variant “HVAC”

C013 Deceleration time

5.00

0.00

{0.02 s}

1300.00 T

if

Variant “HVAC”

Function

The acceleration and deceleration times determine the controller response after a setpoint change.

Adjustment

-

The acceleration and deceleration times refer to a change of the field frequency from 0 Hz to the
max. field frequency set under C011.

-

Calculate the times T

ir

and T

if

, which must be set under C012 and C013.

- t

ir

and t

if

are the times desired for the change between f

d1

and f

d2

.

7

LU

 W

LU

ô

I

GPD[

I

G

Å I

G

7

LI

 W

LI

ô

I

GPD[

I

G

Å I

G

Important

Under unfavourable operating conditions, too short acceleration and deceleration times can lead to
the deactivation of the controller under overload with the indication of TRIP OC5. In these cases, the
acceleration and deceleration times should be set such that the drive can follow the speed profile
without reaching I

max

of the controller.

f /Hz

d

f

dmax

d2

f

fd1

0

tir

tif

Tir

Tif

t

FIG 5-1

Acceleration and deceleration times