Network of several drives

8200SHB0199

10-8

Protection by

F1 ... F3 with alarm contact

Protection of

Cable protection

-

on the mains side

-

on the DC-bus

-

on the motor side

Unit protection in the event of
overload
If a supply/input fails because F1 ... F3
blows, the remaining controllers which
are connected will not be overloaded
as the alarm contact switches off the
mains and thus the whole network.

No unit protection in the event of
short circuit

Possible faults

One or more controllers with

- internal short circuit (+ U

G →

-U

G

)

- internal earth fault (+ U

G →

PE/-U

G →

PE)

- motor-side earth fault on phase W

Risk

Several parallel controllers supply the fault location(s) via the DC-bus. This may lead to overload of the
intact controller, as the faulty controller is not selectively activated on the DC-bus.

-

Possible damage with central and decentral supply
- destruction of the controller concerned
- destruction of the controllers still intact
- destruction of the supply unit

Note

The extent of the destructions depends on the ratio ”DC-bus power of the whole system / rated power of
the controller concerned”.

Protection by

F1 ... F3 with alarm contact + F4 ... F5

Protection of

Cable protection

-

on the mains side

-

on the DC-bus

-

on the motor side

Unit protection in the event of
overload
If a supply/input fails because F1...F3
blows, the remaining controllers which
are connected will not be overloaded
as the alarm contact switches off the
mains and thus the whole network.

Unit protection in the event of
short circuit

Possible faults

One or more controllers with

- internal short circuit (+ U

G →

-U

G

)

- internal earth fault (+ U

G →

PE/-U

G →

PE)

- motor-side earth fault on phase W

Risk

-

Possible damage with central supply
- destruction of the controller concerned

-

Possible damage with decentral supply
- destruction of the controller concerned

Note

The selective activation of the mains and DC side reduces the extent of destruction.