Configuration

8200SHB0199

7-57

Series “HVAC”:

Function

-

DC braking enables fast deceleration of the drive to standstill without using a brake unit.

-

The brake torque is lower as for braking in generator mode (via chopper or DC-bus operation).
- The possible brake torque is approx. 20 % ... 30 % of the rated motor torque.

-

A brake voltage or a brake current can be selected.

-

C196 enables an improved motor start when the automatic DC-injection brake is activated
(e.g. for hoists).

-

The DCB function is activated either automatically when falling below the threshold set under
C019 or via dig. input terminals E1 ... E4 (depending on C007).

-

With the auto-DCB function, also a dead band in the setpoint can be set via C019. If DC
braking is not required here, set C106 = 0.

Adjustment

1.Select, whether a brake voltage (C035 = -0-) or a brake current is to be entered.
2.Select the brake voltage or brake current in per cent under C036.

- With C035 = -0-, the indication refers to the rated controller voltage [V

r

].

- With C035 = -1-, the indication refers to the rated controller current [I

r

].

3.Select how to activate the DC-injection brake (DCB):

- Via terminals E1 ... E4
- Automatically

Activation via terminals
E1 ... E4

Setting C007

High level at

Function

-17-

Terminal E1

*

DCB remains active until a LOW signal is
assigned to terminal E1.

-3-, -7-, -14-, 19

Terminal E2

*

DCB remains active until a LOW signal is
assigned to terminal E2.

-0-, -5-, -11-, -25-,
-29-, -41-, -42-, -48-

Terminal E3

*

DCB remains active until a LOW signal is
assigned to terminal E3.

-31-, -36-, -51-

Terminal E4

*

DCB remains active until a LOW signal is
assigned to terminal E4.

*

The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1).

Automatic activation

1.Select under C106:

- C106 = 0,00 - auto DCB is not active (no reaction on f

d

< C019).

- C106 > 0.00 - the DC injection brake is active for the time set. Afterwards, the drive will set

controller inhibit.

2.Select the input conditions for the automatic DC injection braking under C196.

- C196 = -0- DCB active, if C050 < C019
- C196 = -1- GSB active, if C050 < C019 and setpoint < C019

3.Set the operating threshold under C019.

- The operating threshold indicates, when the DC injection brake is activated (see step 2.).

Important

-

C035 = -1-
- The DC motor current is directly set under C036 (ref. to rated controller current).

-

C035 = -0-
- The DC motor current is indirectly set under C036 (ref. to rated controller voltage).

-

Please observe, that the connected motor can be overheated by overlong operation and excessive
DC-motor current.

Special features

-

Set the operating threshold for auto DCB under C019. The display value of the parameter can be
related to an application datum (C500, C501) (see chapter 7.6.3.)

-

With C106 = 0.00, the automatic DC-injection brake is not active.

-

C035 and C196 are only stored in parameter set 1.