Application examples

8200SHB0199

15-1

15 Application examples

15.1

Pump application with pressure control

K14

K12

K11

Ctrl.
enable

Down

JOG

L

M

3~

Frequency inverter 8210/8220/8240

Pressure setpoint
e.g. from PC/PLC/
keypad

Fault message
e.g. PLC

Analog display for
actual pressure

Actual pressure

-

+

p

Pressure sensor

0 ... 10 V, 0/4 ... 20 mA

(external aux. energy/

supply required

Pump

W

K35.0144_gba

V
U

Z1

K1

F1

Z2

L1L2L3

Up

H/RE

28
E1

E3

E2

E4

20

62

7

8

9

X1

2101

W

V
U

G

-U

G

+U

L1

L2

L3

PE

FIG 15-1

Application of a pump with pressure control

Z1

Mains filter required for radio interference level A or B. For mains chokes see chapter 3.4 ff.

Z2

Motor filter/sine filter required for long motor cables or motors not designed for inverter operation
(see chapter 4.2.7.2).

Shield all signal and motor cables. Please observe the corresponding installation instructions given in chapters 4.2
and 4.3.