Commissioning – Lenze 8200 Frequency inverters User Manual

Page 114

Advertising
background image

Commissioning

8200SHB0199

5-9

4.Set slip compensation

(C021):

Rough setting according to motor data:

4.Set slip compensation

(C021):

s



n

Nsyn

Å n

r

n

Nsyn

ô 100 %

n

Nsyn



f

dr

ô 60

p

s

Slip constant (C021)

n

Nsyn

Synchronous motor speed [min

-1

]

n

r

Rated speed to motor nameplate [min

-1

]

f

dr

Rated frequency to motor nameplate [Hz]

p

No. of pole pairs (1, 2, 3, ...)

Precise setting:

-

Correct C021 until no load-dependent speed drop occurs in the required speed range between
idle running and max. motor load.

-

If the values under C021 are too high, the drive may become instable (overcompensation).

-

In the field frequency range between 5 Hz ... 50 Hz (87 Hz) the deviation of the rated speed is

$ 1 %(guide value). In field-weakening operation, the fault increases.

Important

-

The change from V/f-characteristic control to motor-current control should only be carried out
when the controller is inhibited.

-

The idle current of the motor (magnetising current) must not exceed the rated current of the
controller.

-

With very small friction values, it is possible that a phase offset of up to 180

• occurs at the motor

shaft when enabling the controller.

Show/Hide Bookmarks

Advertising