6 display functions, 1 display values, 2 switch-on display – Lenze 8200 Frequency inverters User Manual

Page 199: Display functions, Display values, Switch-on display, Configuration

Advertising
background image

Configuration

8200SHB0199

7-62

7.6

Display functions

7.6.1

Display values

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C040 Controller enable

*

-0-

Controller inhibited

-1-

Controller enabled

HVAC only

*see Operating
Instructions 2102

C046 Frequency setpoint

*

-480.00

{0.02 %}

480.00 [Hz]

HVAC only

C047* Current setpoint

I

max

limit value

[%]
HVAC only

Display only
150 % for rated value
at term. 8 and factory
setting

C049* Additional setpoint

[Hz]
HVAC only

Display only

-

Only if C005 = -1-,
-2-

C050* Output frequency

[Hz]

Display only

C051* Actual PID controller

value

[Hz]
HVAC only

Display only

C052* Motor voltage

[V]

Display only

C053* DC-bus voltage

[V]
HVAC only

Display only

C054* Motor current

[A]

Display only

C056* Unit load

[%]

Display only

C061* Temperature

Heat sink

[°C]

Display only

Function

Some parameters, which are measured by the controller during operation, can be displayed on the
8201BB operating module.

Important

Series “HVAC”:

-

Display under C050 corresponds to the setpoint without slip compensation (C021).

-

Display under C047:
- If C005 = -0-, -1-, -2-, -6-, -7-,

“ I

max

limit value (C022).

-

Display under C049, only if C005 = -1- and -2-.

Special features
821X/822X/824

Series “HVAC”:

-

The display value of a parameter can be related to an application datum (see chapter 7.6.3).

-

Codes C046, C049, C050, C051:
Hz display only in factory setting (C500 = 2000; C501 = 10)
(see chapter 7.6.3).

7.6.2

Switch-on display

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C004

¤ Switch-on display

-0-

-0-

Field frequency f

d

(C050)

-1-

Unit load (C056)

-2-

Motor current (C054)

Function

The here selected display is active after mains connection, if the 8201BB operating module is
plugged on.

Show/Hide Bookmarks