11 setpoint input, 1 analog setpoint input, Setpoint input – Lenze 8200 Frequency inverters User Manual

Page 177: Analog setpoint input, Configuration

Advertising
background image

Configuration

8200SHB0199

7-40

7.5.11

Setpoint input

7.5.11.1 Analog setpoint input

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C026 Offset adjustment

analog input

0.00

-10.00

{0.01 V}

10.00 HVAC only

Not effective with
C005 = -0-

C027 Scaling factor of

analog input

100.0

-200.0

{0.1 %}

200.0 HVAC only

Not effective with
C005 = -0-

C034

¤ Master current

-0-

-0-

0 mA ... 20 mA /
0 V ... 5 V / 0 V ... 10 V

-1-

4 mA ... 20 mA

Function

An analog setpoint signal can be selected via terminal 8.

-

You can select different setpoint ranges by reconnection of the jumper at the front of the
controller.

-

Inverse setpoint input because of negative terminal adjustment.

-

Offset adjustment of the analog channel (only series “HVAC”)

Adjustment

Setpoint range

Jumper position

0 mA ... 20 mA / 4 mA ... 20 mA
0 V ... 5 V
0 V ... 10 V

5 - 6
3 - 4
1 - 2

(Factory setting)

To select the setpoint by means of the master current, you change the ranges under C034:
C034 = -0-

0 mA ... 20 mA

C034 = -1-

4 mA ... 20 mA

Important

-

With an internal reference voltage of 5 V:
- Plug in the jumper at position 3-4

-

If the setpoint is input by means of a master voltage 0 V ... 5 V / 0 V ... 10 V:
- Set C034 = -0-

-

Analog setpoint input is not possible with setpoint input via the function ”Motor potentiometer”
(C007 = -10-, -11-, -12-, -13-, -21-).