2 vmin setting, Vmin setting, Configuration – Lenze 8200 Frequency inverters User Manual

Page 161: Setting

Advertising
background image

Configuration

8200SHB0199

7-24

7.5.6.2

V

min

setting

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C016 V

min

setting

C016

820X

*

0.00

{0.05 %}

40.00

*depends on the unit

821X/822X/

824X

0.00

0.00

{0.02 %}

40.00

Function when
C014 = -0-, -1-

Load-dependent boost of the motor voltage in the field frequency range below the V/f-rated
frequency. C016 acts as gain factor of the auto-boost function (only with 820xE).

Adjustment

As known from experience, an adjustment is not required when having the conditions mentioned
above.
An optimisation can be advantageous
for drives with very high starting torques:
1.Operate motor under load.
2.Select the frequency setpoint.
3.Increase V

min

until the required motor current (torque) occurs.

- If the setting of V

min

is too high, a positive-feedback effect can occur and activate the TRIP

”overcurrent” (OCx).

for drives with square load torques (fans, pumps):
1.Operate motor under load.
2.Select the frequency setpoint.
3.Adapt V

min

until the drive runs steadily and smoothly over the whole frequency range.

- If the setting of V

min

is too high, the TRIP ”overcurrent” (OCx) can be activated and lead to an

excessive motor temperature.

for drives with special motors:
1.Operate motor under load.
2.Select the frequency setpoint.
3.Increase V

min

until the required motor current (torque) occurs.

- If the setting of V

min

is too high, a positive-feedback effect can occur and activate the TRIP

”overcurrent” (OCx).

4.Check the current consumption during idle running when no load is applied.