9 digital frequency input, Digital frequency input, Configuration – Lenze 8200 Frequency inverters User Manual

Page 197: Only “hvac” controllers

Advertising
background image

Configuration

8200SHB0199

7-60

7.5.14.9 Digital frequency input

Only “HVAC” controllers

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze Choice

Info

IMPORTANT

C425

¤* Adjustment of

digital frequency

-2-

Dig.-freq. Resolution Scanning Max.-freq.

-0-

100 Hz

1/200

1 s

300 Hz

-1-

1 kHz

1/200

100 ms

3 kHz

-2-

10 kHz

1/200

10 ms

10 kHz

-3-

10 kHz

1/1000

50 ms

10 kHz

-4-

10 kHz

1/10000

500 ms

10 kHz

C426* Gain adjustment

frequency input E1

100.0 -200.0

{0.1 %}

200.0

C427 Offset adjustment

frequency input E1

0.0

-12.5

{0.1 %}

12.5

Function

Select a digital frequency of 0 Hz ... 10 kHz as setpoint or as actual value using terminal E1.
With C007 = -28- ... -45-, -48-, -49-, -50-, -51-, the terminal E1 is configured for this function.

Adjustment

-

C425
- Selection of the frequency to be assigned to terminal E1.
- Resolution and scanning time for reading the frequency.

-

C426
- Sets the gain of the input signal. 100 % corresponds to a gain factor = 1.
- If E1 is used as actual value, C426 must be set as positive value, e.g. for pressure control, if the

motor speed is to increase when the pressure falls.

-

C427
- Sets the offset of the input signal.
- If C427 = -12.5 %, an offset of -20 % is internally set for the input.

-

Select input E1 for master current 4 mA ... 20 mA:
- Use an analog plug-in module 8279.
- Set C426 = 125 %.
- Set C427 = -12.5 %.

Important

-

When using the analog input module 8279 for the frequency input E1:
- Set C425 = -2-, -3- or -4-.

-

With C005 = -0-, C425 and C426 are not active.

-

C425, C426, C427 are only stored in parameter set 1.

Special features

-

For higher accuracy requirements at 10 kHz digital frequency, select a higher resolution under
C425 taking into account the scanning time.

-

After addition to the signal at terminal E1, the offset (C427) is only effective as positive value
(see signal flow-chart in chapter 16.3.2, as of software version 3.0).

-

The digital frequency refers to internal normalisation (e.g. C011 etc.)

-

The maximum frequency is the maximum to be processed by the input E1. If the value is
exceeded, it must be adapted proportionally under C426.

Show/Hide Bookmarks

Advertising