3 general data/ application conditions, General data/application conditions, Technical data – Lenze 8200 Frequency inverters User Manual

Page 36: 3 general data/application conditions

Advertising
background image

Technical Data

8200SHB0199

3-4

3.3

General data/application conditions

Field

Values

Vibration resistance

Germanischer Lloyd, general conditions

Humidity class

Humidity class F without condensation (average relative humidity 85 %)

Permissible temperature
range

During transport of the controller:

-25

•C¡+70 •C

Permissible temperature
range

During storage of the controller:

-25

•C¡+55 •C

During operation of the controller:

0

•C¡+40 •C

+ 40

•C¡+50 •C

without power derating
with power derating

Permissible installation
height

h

$ 1000 m a.m.s.l.

1000 m a.m.s.l.

h $ 4000 m a.m.s.l.

without power derating
with power derating

Degree of pollution

VDE 0110 part 2 pollution degree 2

Noise emission

Requirements to EN 50081-2, EN 50082-1, IEC 22G-WG4 (Cv) 21
Limit value class A to EN 55011 (industry) with mains filter
Limit value class B to EN 55022 (residential area) with mains filter and installation into control
cabinet

Noise immunity

Limit values maintained with mains filter
Requirements to EN 50082-2, IEC 22G-WG4 (Cv) 21
Requirements

Standard

Severities

ESD

EN61000-4-2

3, i.e. 8 kV with air discharge,
6 kV with contact discharge

RF interference (enclosure)

EN61000-4-3

3, i.e. 10 V/m; 27

¡1000 MHz

Burst

EN61000-4-4

3/4, i.e. 2 kV/5 kHz

Surge
(Surge on mains cable)

IEC 1000-4-5

3, i.e. 1.2/50

³s,

1 kV phase-phase,
2 kV phase-PE

Insulation strength

Overvoltage category III to VDE 0110

Packaging to DIN 4180

Types 820X, 821X, 824X
Types 822X,
821X/2X/4X HVAC (V020)

Dust packaging
Transport packaging

Enclosure

Types 82XX, 82XX HVAC (V020)

IP20
NEMA 1: Protection against contact

Types 8215 - 8218, 822X, 824X,
8215/16/17/18/2X/4X HVAC (V020)

IP41 on the heat-sink side with thermal separation in
push-through technique

Approvals

Types 82XX, 82XX HVAC (V020)

CE:

Low-Voltage Directive and
Electromagnetic Compatibility

Types 822X, 824X,
822X/4X HVAC (V020)

UL 508:
UL 508C:

Industrial Control Equipment
Power Conversion Equipment

Show/Hide Bookmarks

Advertising