8200SHB0199

7-38

7.5.10.1 Reset integral component and influence

Function

The following functions are possible:

-

Reset the integral component K

I

of the PID controller via terminal.

-

Set the influence of the PID controller to 0.

Activation

C007 = -28- ... -34-, -48-, -50-, -51-:

-

HIGH level at terminal E2
- Reset of K

I

C007 = -48-, -49-, -50-:

-

HIGH level at terminal E4
- Reset influence

The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)

7.5.10.2 Setpoint selection for the process controller

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C181* Setpoint PID

controller

0.00

-480.00

{0.02 Hz}

480.00

Function

Selection of a frequency setpoint, e.g. for

-

the dancer position for a dancer control in a line drive,

-

the pressure setpoint in a pressure control.

Adjustment

C181 = 0

-

The setpoint of the PID controller is
- selected externally (terminal 8 or E1),
- set via the keys (▲, ▼) of the operating module 8201BB.

C181

 0

-

Setpoint selection for the PID controller via this code.

Important

-

The setpoint selection via this code is only active, if C181

 0.

-

C181 is only stored in parameter set 1.

Special features

-

The setpoint can also be entered as application datum (C500, C501) (see chapter 7.6.3).