3 change of the direction of rotation (cw/ ccw), Change of the direction of rotation (cw/ccw), Configuration – Lenze 8200 Frequency inverters User Manual

Page 191: 3 change of the direction of rotation (cw/ccw)

Advertising
background image

Configuration

8200SHB0199

7-54

7.5.14.3 Change of the direction of rotation (CW/CCW)

Not failsafe change of the direction of rotation

Function

Settings
C007 = -0- ... -13-, or
C007 = -0- ... -13-, -23-, -43-, -45- (only series “HVAC”)
enable the change of the motor direction via terminal E4.
The change depends on

-

the set times T

ir

(C012) and T

if

(C013),

-

the connected ramp function generator S-shape (C182). (Series “HVAC”)

Adjustment

When connecting the controller in phase

-

a CW field of rotation will occur at LOW signal,

-

a CCW field of rotation will occur at HIGH level.

Series “HVAC”: The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1).

Important

-

In the event of wire breakage or a failure of the external voltage supply, the direction of rotation
can be changed.

-

CW/CCW changeover only in the main setpoint.

Failsafe change of the direction of rotation

Function

Settings
C007 = -14- ... -22-, or
C007 = -14- ... -22-, -34-, -47- (only series “HVAC”)
enable the failsafe change of the direction of rotation via terminals E3 and E4.
The change depends on

-

the set times T

ir

(C012) and T

if

(C013),

-

the connected ramp function generator S-shape (C182). (Series “HVAC”)

Adjustment

Function

E3

*

E4

*

CCW rotation

LOW

HIGH

CW rotation

HIGH

LOW

Quick stop

LOW

LOW

Unchanged

HIGH

HIGH

*

Series “HVAC”: The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1).

Important

-

If a HIGH signal is assigned to terminals E3 and E4, the terminal signal which was activated first
determines the direction of rotation.

-

If a HIGH signal is assigned to terminals E3 and E4 when connecting the mains, the controller
will activate the quick stop function.

-

CW/CCW changeover only in the main setpoint.

-

For speed control with actual value feedback, the CW/CCW changeover is not possible.