Installation – Lenze 8200 Frequency inverters User Manual
Page 87
![background image](/manuals/566230/87/background.png)
Installation
8200SHB0199
4-30
Types 8221/8222/8223
PE
T1
T2
U
V
W
Correct screen connection with screened cables:
-
Fix the screen of the motor cable and thermal
contact. Do not use as a strain relief!
-
To improve the screen connection: Connect the
screen additionally to the stud PE next to the
controller.
Types 8224/8225
T1
T2
PE
U
V
W
M5 X 12
-
Strain relief by using cable binders
➀
.
-
Correct screen connection with screened cables:
- Apply motor cable screen to the screening
plate using clamp and screws M5x12
➁
.
- Connect thermal contact screen to the stud PE
next to the motor connection over a large
surface.
Types 8226/8227
T1
T2
PE
U
V
W
M5 X 12
M4 X 12
-
Strain relief by using cable clamps and screws
M4x12
➂
.
- An additional strain relief/fixing is possible with
cable binders
➀
.
-
Correct screen connection with screened cables:
- Apply motor cable screen to the screening
plate using clamp and screws M5x12
➁
.
- Connect thermal contact screen to the stud PE
next to the motor connection over a large
surface.
FIG 4-17
Proposal for motor connection with 822X
Show/Hide Bookmarks