Configuration – Lenze 8200 Frequency inverters User Manual

Page 205

Advertising
background image

Configuration

8200SHB0199

7-68

Switching conditions

Monitoring functions

Relay

Ready for operation

energised when controller is ready

drop-out when

-

TRIP fault message

-

Undervoltage/overvoltage

TRIP fault message

energised with TRIP fault message

Motor is running

energised when f

d

 0 Hz

Motor is running / CW rotation;
Motor is running / CCW rotation

energised when f

d

 0 Hz, direction of rotation via terminal

CCW rotation: f

d

> 0 Hz,

CW rotation: f

d

< 0 Hz

Field frequency f

d

= 0

energised when f

d

= 0 Hz, because

-

f

dset

= 0 Hz, t

if

over

-

DC-injection brake active

-

Controller inhibited

f

dset

reached

energised when f

d

= f

dset

Q

min

reached

energised when f

d

> f

dQmin

(C017)

I

max

reached

energised when motor current =

-

I

max

motor mode (C022)

-

I

max

generator mode (C023)

Overtemperature

energised when the heat sink temperature =

J

max

-10

•C

TRIP, Q

min

or IMP

(only “HVAC” controllers)

drop-out when

-

TRIP fault message

-

f

d

$ f

dQmin

-

Pulse inhibit because of controller inhibit, overvoltage or
undervoltage

PTC warning
(only “HVAC” controllers)

drop-out when

-

connected PTC thermistor has detected motor overtemperature.

Apparent motor current
< current threshold
(only “HVAC” controllers)

drop-out when I

motor

(C054) < current threshold (C156)

Apparent motor current
< current threshold and
f

d

> Q

min

-threshold (C017)

(only “HVAC” controllers)

drop-out when I

motor

(C054) < current threshold (C156) and

f

d

> f

dQmin

(C017)

Apparent motor current
< current threshold and
ramp-function generator input =
ramp-function generator output
(only “HVAC” controllers)

drop-out when I

motor

(C054) < current threshold (C156) and

ramp-function generator input = ramp-function generator output

Warning motor phase failure
(only “HVAC” controllers)

energised in the event of a motor-phase failure

f

d

(C050) < f

dmin

(C010)

(only “HVAC” controllers)

energised when f

d

> C010

Show/Hide Bookmarks