6 parameter set changeover par, 7 trip set, Parameter set changeover par – Lenze 8200 Frequency inverters User Manual

Page 195: Trip set, Configuration

Advertising
background image

Configuration

8200SHB0199

7-58

7.5.14.6 Parameter set changeover PAR

Function

Switches between the two parameter sets (ONLINE) during controller operation.

Activation

Series “HVAC”:

C007 = -4-, -8-, -15-, -17, -18-, or
C007 = -4-, -8-, -15-, -17-, -18-, -35-, -36-, -37-, -44-, -45- (only series “HVAC”)

- LOW level at terminal E2 activates PAR1
- HIGH level at terminal E2 activates PAR2

C007 = -1-, -3-, -6-, -7-, -12-, or
C007 = -1-, -3-, -6-, -7-, -12-, -24-, -33-, -38-, -46-, -51- (only series “HVAC”)

- LOW level at terminal E3 activates PAR1
- HIGH level at terminal E3 activates PAR2

The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)

Important

-

In the code level the active code set is indicated by blinking of ”PAR1” or ”PAR2”.

-

The codes marked with *in the code table are similar for PAR1 and PAR2. The active parameter
set is only displayed on the operating module in the code level.

-

For changeover between the parameter sets via terminal, the same terminal of both parameter
sets must be assigned with PAR.

Special features

821X/822X/824X

If the control mode (C014) is set differently in the parameter sets, the parameter sets should only be
changed when the controller is inhibited.

7.5.14.7 TRIP set

Function

If the function TRIP set is activated, the unit detects external faults that can thus be taken into
account. The controller indicates the fault EEr and sets controller inhibit.

Activation

-

C007 = -7-, -8-, -18-, -19-:
- LOW level at terminal E1

-

C007 = -5-, -6-, -9-, -20-, or
C007 = -5-, -6-, -9-, -20-, -38-...-43- (only series “HVAC”):
- LOW level at terminal E2

-

C007 = -10-, or
C007 = -10-, -27- (only series “HVAC”):
- LOW level at terminal E3

-

C007 = -32-:
- LOW level at terminal E4 (only series “HVAC”)

Series “HVAC”:

The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)

Important

For fault reset, see chapter 8.4, ”Reset of fault messages”.

Special features

820X

With the operating mode ”control via LECOM” (C001 = -3-), the function TRIP set cannot be
activated via terminals.

821X/822X/824X
Series “HVAC”:

-

Independently of the operating mode C001, TRIP set can always be activated via terminals.

-

The activation of TRIP set via terminals can be switched-off with the priority mask (C115).