Commissioning – Lenze 8200 Frequency inverters User Manual

Page 116

Advertising
background image

Commissioning

8200SHB0199

5-11

3.Set V

min

boost (C016).

Load-dependent boost of the motor voltage in the field frequency range below the V/f-rated
frequency. C016 acts as gain factor of the auto-boost function.

Adjustment
In general, an adjustment is not necessary. An optimisation can be advantageous:
For drives with very high starting torques:
A Operate the motor under load.
B Select the frequency setpoint.
C Increase V

min

until the required motor current (torque) occurs.

If the setting of V

min

is too high, a positive-feedback effect can occur and activate the TRIP

”overcurrent” (OCx).

For drives with square load torques (fans, pumps):
A Operate the motor under load.
B Select the frequency setpoint.
C Adapt V

min

until the motor is running steadily and smoothly over the whole frequency range.

If the setting of V

min

is too high, the TRIP ”overcurrent” (OCx) can be activated and lead to an

excessive motor temperature.

For drives with special motors:
A Operate the motor under load.
B Select the frequency setpoint.
C Increase V

min

until the required motor current (torque) occurs.

If the setting of V

min

is too high, a positive-feedback effect can occur and activate the TRIP

”overcurrent” (OCx).

D Check the current consumption during idle running when no load is applied.

4.Set the slip compensation

(C021).

Rough setting according to motor data:

4.Set the slip compensation

(C021).

s



n

Nsyn

Å n

r

n

Nsyn

ô 100 %

n

Nsyn



f

dr

ô 60

p

s

Slip constant (C021)

n

Nsyn

Synchronous motor speed [min

-1

]

n

r

Rated speed to motor nameplate [min

-1

]

f

dr

Rated frequency to motor nameplate [Hz]

p

No. of pole pairs (1, 2, 3, ...)

Precise setting:

-

Correct C021 until no load-dependent speed drop occurs in the required speed range between
idle running and max. motor load.

-

If the values under C021 are too high, the drive may become instable (overcompensation).

-

In the field frequency range between 5 Hz ... 50 Hz (87 Hz) the deviation of the rated speed is

$ 1 %(guide value). In field-weakening operation, the fault increases.

Show/Hide Bookmarks