Configuration – Lenze 8200 Frequency inverters User Manual

Page 226

Advertising
background image

Configuration

8200SHB0199

7-89

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Choice

Lenze

Name

C021 Slip compensation

0.0*

-50.0

{0.1 %}

50.0 Page 7-28

* If C014 = -2-, -3-,

controller dependent

C021 Slip compensation

0.0*

-50.0

{0.1 %}

50.0 Page 7-28

* If C014 = -2-, -3-,

controller dependent

0.0

0.0

{0.1 %}

20.0

If C014 = -4-

C022 I

max

limit

(motor mode)

150

30

{1 %}

150 Page 7-17

C023 I

max

limit

(generator mode)

80

30

{1 %}

150 Page 7-17

The current-limit
controller for operation
in generator mode is
not active at 30 %.

C026 Offset adjustment

analog input

0.00

-10.00

{0.01 V}

10.00 Page 7-40

C026 < 0 V

-

f

dmin

can fall below

the value set under
C010

C027 Scaling factor of

analog input

100.0

-200.0

{0.1 %}

200.0 Page 7-40

C034

¤ Master current

-0-

-0-

0 to 20 mA /
0 to 5 V / 0 to 10 V

-1-

4 to 20 mA

Page 7-40

C035*

¤ Selection DC brake

-0-

-0-

Selection of brake voltage under
C036

-1-

Selection of brake current under
C036

Page 7-56

C036 Voltage/current for

DCB

*

0.00

{0.02 %}

150.00 Page 7-56

*depends on the unit

C037

œ JOG value 1

20.00

-480.00

{0.02 Hz}

480.00 Page 7-43

C038

œ JOG value 2

30.00

-480.00

{0.02 Hz}

480.00 Page 7-43

C039

œ JOG value 3

40.00

-480.00

{0.02 Hz}

480.00 Page 7-43

C040 Controller enable

*

-0-

Controller inhibited

-1-

Controller enabled

Page 7-62

C043 TRIP reset

*

-0-

No current fault

-1-

Current fault

*see Operating
Instructions 2102

C046

œ Frequency setpoint

*

-480.00

{0.02 %}

480.00 Page 7-62

Instructions 2102

C047* Current setpoint

I

max

limit value

Page 7-62

Display only [%]
I

max

limit value (C022)

C049*

œ Additional setpoint

Page 7-47,

7-62

Display only

-

Only if C005 = 1, 2

C050*

œ Output frequency

Page 7-62

Display only

C051*

œ Actual PID controller

value

Page 7-34,

7-62

Display only

C052* Motor voltage

Page 7-62

Display only [V]

C053* DC-bus voltage

Page 7-62

Display only [V]

C054* Motor current

Page 7-62,

7-65

Display only [A]

C056* Unit load

Page 7-62

Display only [%]

C061* Heat sink

temperature

Page 7-62

Display only [°C]

Show/Hide Bookmarks

Advertising