3 types 822x, Types 822x, Technical data – Lenze 8200 Frequency inverters User Manual

Page 51

Advertising
background image

Technical Data

8200SHB0199

3-19

3.5.3

Types 822X

120 % overload

Type

8221

8222

8223

1)

8224

8225

1)

8226

8227

1)

Mains current
with mains filter/mains choke

I

mains

[A]

39.0

50.0

60.0

97.0

119

145

185

Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V

$ V

DC

$ 620 V

Motor power (4 pole ASM)
at 4 kHz/8 kHz

*

P

r

[kW]

22

30

37.5

55

75

90

110

Motor power (4 pole ASM)
at 4 kHz/8 kHz

*

P

r

[hp]

30

40

50

74

100

120

148

Output power U, V, W
at 4 kHz/8 kHz

*

S

r4

[kVA]

S

r8

[kVA]

29.8
22.2

39.5
32.6

46.4
41.6

74.8
61.7

91.5
76.2

110

103.9

142

124.7

Output
current

4 kHz

*

I

r4

[A]

43

56

66

100

135

159

205

Output
current

8 kHz

*

I

r8

[A]

32

47

59

89

110

150

171

12 kHz

*

I

r12

[A]

27

40

50

62

88

120

126

16 kHz

*

I

r16

[A]

24

35

44

54

77

105

108

Noise optimised 4 kHz

*3)

I

r4

[A]

32

47

59

89

110

150

159

4)

Noise optimised 8 kHz

*3)

I

r8

[A]

29

43

47

4)

59

4)

76

4)

92

4)

100

4)

Noise optimised 12 kHz

*

I

r12

[A]

25

37

44

54

66

82

90

Noise optimised 16 kHz

*

I

r16

[A]

21

30

35

46

60

67

72

Max.
output

4 kHz

*

I

rmax4

[A]

48

70.5

89

134

165

225

270

Max.
output
current

8 kHz

*

I

rmax8

[A]

48

70.5

89

134

165

225

221

current
for

12 kHz

*

I

rmax12

[A]

40

59

75

92

114

156

164

for
60 s

2)

16 kHz

*

I

rmax16

[A]

36

53

66

81

100

136

140

60 s

2)

Noise optimised 4 kHz

*3)

I

rmax4

[A]

48

70.5

89

134

165

225

238

4)

Noise optimised 8 kHz

*3)

I

rmax8

[A]

43

64

70

4)

88

4)

114

4)

138

4)

150

4)

Noise optimised 12 kHz

*

I

rmax12

[A]

38

56

66

81

85

107

117

Noise optimised 16 kHz

*

I

rmax16

[A]

31

46

53

69

78

87

94

Power loss (operation with I

r4

)

P

loss

[W]

640

810

810

1350

1470

2100

2400

1)

Max. permissible ambient operating temperature + 35

•C

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I

rx

.

3)

Only with variant “HVAC”

4)

Must only be operated with C144 = -1- (automatic chopper frequency derating at

J

max

= + 5

•C). Ensure not to

exceed the currents.

*

Chopper frequency of the inverter

For more data, see chapter 3.4.4 and chapter 3.4.5.

Show/Hide Bookmarks

Advertising