Installation

8200SHB0199

4-42

4.2.8.4

Connection diagrams: Analog plug-in module

Note!

Only controllers of the series 8210, 8220 and 8240 HVAC can be equipped with
an analog plug-in module.

62 7

8

9 K11K12K14

20 28 E1 E2 E3 E4 39

821X/822X/824X HVAC (V020)

20 28 E1 E2 E3 E4 39

8279

R

K3501421

3K

GND2

GND1

VCC15

5%

0 ... 10 V

0 ... 20 mA

4 ... 20 mA

Connection
Voltage supply for the 8279 plug-in module:

-

Plug the module on the controller.

-

Bridge terminals 7 and 39.

Note:
With this type of wiring there are 2 or more wires connected to
one terminal. To avoid this, provide an external connection facility.

FIG 4-26

Control connections: Supply with internal control voltage

62 7

8

9 K11K12K14

20 28 E1 E2 E3 E4 39

821X/822X/824X HVAC (V020)

20 28 E1 E2 E3 E4 39

8279

R

K3501422

3K

GND2

GND1

VCC15

5%

12 ... 30V

0 ... 10 V

0 ... 20 mA

4 ... 20 mA

Danger!
There is no mains isolation between external supply and unit
mass.
There is no double mains isolation between the mains and the
terminals.
Therefore, the unit is not electrically isolated, i.e. not protected
against contact.

Connection
Voltage supply for the 8279 plug-in module:

-

Plug the module on the controller.

-

Bridge terminals 7 and 39.

Note
With this type of wiring there are 2 or more wires connected to
one terminal. To avoid this, provide an external connection facility.

FIG 4-27

Control connections: Supply with external control voltage (+12 V ... +30 V)

GND1

Reference for internal voltages

GND2

Reference for external voltages

GND1 and GND2 have a potential isolation inside the unit.