Technical Data

8200SHB0199

3-9

150 % overload

Type

8215

8216

8217

8218

Order No.

EVF8215-E

EVF8216-E

EVF8217-E

EVF8218-E

Variant ”Cold Plate”

Type

8215-V003

8216-V003

8217-V003

8218-V003

Variant ”Cold Plate”

Order No.

EVF8215-C-V003 EVF8216-C-V003 EVF8217-C-V003 EVF8218-C-V003

Variant “HVAC”

Type

8215-V020

8216-V020

8217-V020

8218-V020

Order No.

EVF8215-E-V020 EVF8216-E-V020 EVF8217-E-V020 EVF8218-E-V020

Motor voltage

3)

V

M

[V]

0 - 3 x V

mains

/ 0 Hz

¡ 50 Hz, if required up to 480 Hz

Power loss (operation with I

rx

)

P

loss

[W]

150

200

280

400

Power derating

[%/K]

[%/m]

40

•C < T

V

< 50

•C: 2.5 %/K

1000 m a.m.s.l.

h $ 4000 m a.m.s.l.: 5 %/1000 m

Field
frequency

Resolution

Absolute

0.02 Hz

Field
frequency Digital setpoint selection

Accuracy

á0.05 Hz

Analog setpoint selection

Linearity

á0.5 %(max. selected signal level: 5 V or 10 V)

Analog setpoint selection

Temperature
sensitivity

0

¡ 40 •C: +0.4 %

Offset

á0 %

Weight
”Cold Plate” without heat sink
”Cold Plate” with heat sink

m [kg]

5.3
2.8

20.8

5.3
2.8

20.8

5.3
2.8

20.8

5.3
2.8

20.8

Printed in bold

Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I

rx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

4)

Only with variant “HVAC”

*

Chopper frequency of the inverter

Show/Hide Bookmarks