9 code table for fihvacfl series, Code table for “hvac” series, Configuration – Lenze 8200 Frequency inverters User Manual

Page 222: 9 code table for “hvac” series

Advertising
background image

Configuration

8200SHB0199

7-85

7.9

Code table for “HVAC” series

How to read the code table:

Column

Abbreviation

Meaning

Code

C013

Code C013

-

The parameter of the code can be different in PAR1 and PAR2.

-

The parameter value is accepted immediately (ONLINE).

C009*

-

The parameter value of the code is always the same in PAR1 and PAR2, but is
always displayed in PAR1.

C001

¤

-

The parameter value of the code will be accepted after pressing SH+ PRG.

[C002]

-

The parameter value of the code will be accepted after pressing SH+ PRG, but
only if the controller is inhibited.

C010

œ

-

Parameter value of the code will only be displayed in [Hz], if C500 = 2000 and
C501 = 10 (factory setting). See chapter 7.6.3.

Name

821X

Name of the code.
Controller-specific setting possibilities (here for 821X).
Without unit designation, the code is valid for all unit types.

Lenze

Factory setting of the code

*

The column ”Important” contains further information.

Choice

1

{1 %}

99 Min. value

{Steps/Unit}

Max. value

Info

-

Meaning of the code

IMPORTANT

-

Additional, important explanation of the code

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C001

¤ Operating mode

-0-

-0-

Setpoint selection via term. 8
Control via terminals
Parameter setting via 8201BB

-1-

Setpoint selection via 8201BB or
LECOM
Control via terminals
Parameter setting via 8201BB

-2-

Setpoint selection via term. 8
Control via terminals
Parameter setting via LECOM

-3-

Setpoint selection via LECOM
Control via LECOM
Parameter setting via LECOM

Page 7-9,

7-42

[C002]* Parameter set

-0-

-0-

Function executed

-1-

Overwrite PAR1 with factory setting

-2-

Overwrite PAR2 with factory setting

-3-

Overwrite PAR1 and PAR2 with the
data of the operating module

-4-

Overwrite PAR1 with the data of the
operating module

-5-

Overwrite PAR2 with the data of the
operating module

-6-

Transmit PAR1 and PAR2 to the
operating module

-7-

Overwrite PAR1, PAR2 and the
unit-dependent data (C016, C036,
C088, C091) with the data of the
operating module

Page 7-10