background image

Installation

8200SHB0199

4-15

4.1.5.2

Demands on the cooler

Coolers, which can be operated with different coolants (air, water, oil, etc.),
can dissipate the power loss of the controller.

In addition to the features required by the user, the following features are
important for safe operation:

-

Good thermal connection with the cooler

- The contact surface between cooler and controller must be at least as

large as the cold plate of the controller.

- Smooth contact surface: approx. 0.05 mm

- Connect cooler and cold plate by means of the provided screws.

- For further information see chapter 4.1.5.4 ff.

-

Observe the thermal resistance R

thmin heat sink

(transition cooler - coolant)

according to the table. The values are valid for

- the operation of controllers under rated conditions (see chapter 3.4),

- a max. temperature of the cold plate of 75

E

C, measuring point: see

FIG 4-11, FIG 4-13, FIG 4-14.

Controller / brake
units

Cooling path

Controller / brake
units

Power to be dissipated P

loss crtl

[W]

R

thmin heat sink

[K/W]

8215-V003

135

0.25

8216-V003

180

0.19

8217-V003

250

0.14

8218-V003

360

0.10

8221-V003

410

0.085

8222-V003

610

0.057

8241-V003

24

1.45

8242-V003

42

0.85

8243-V003

61

0.57

8244-V003

105

0.33

8245-V003

180

0.19

8246-V003

360

0.10

9351-V003

100

0.3

9352-V003

63

0.3