3 adapt machine data, 1 determine speed range (fdmin, fdmax), Adapt machine data – Lenze 8200 Frequency inverters User Manual

Page 108: Determine speed range (fdmin, fdmax), Commissioning, 1 determine speed range (f

Advertising
background image

Commissioning

8200SHB0199

5-3

5.3

Adapt machine data

5.3.1

Determine speed range (f

dmin,

f

dmax)

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C010 Minimum field

frequency

820X

0.00

0.00

{0.05 Hz}

480.00

821X/822X/

824X

0.00

0.00

{0.02 Hz}

480.00

C011 Maximum field

frequency

820X

50.00

30.00

{0.05 Hz}

480.00

821X/822X/

824X

50.00

7.50

{0.02 Hz}

480.00

Function

The speed range required for the application can be selected via the input of field frequencies f

dmin

and f

dmax

:

-

f

dmin

corresponds to the speed at 0 % speed setpoint selection.

-

f

dmax

corresponds to the speed at 100 % speed setpoint selection.

Adjustment

Relation between field frequency and synchronous motor speed:

n

Nsyn

f

dmax

ô 60

p

n

Nsyn

Synchronous motor speed [min

-1

]

f

dmax

Max. field frequency [Hz]

p

No. of pole pairs (1, 2, 3, ...)

Example: 4 pole asynchronous motor:
p = 2, f

dmax

= 50 Hz

n

Nsyn

50

ô 60

2

1500 min

Å1

Important

-

With the setting of f

dmin

> f

dmax

, the field frequency is limited to f

dmax

.

-

With setpoint selection via JOG values, f

dmax

acts as limitation.

-

f

dmax

is an internal normalisation variable:

- Use the LECOM interface only for important modifications, when the controller is inhibited.

-

Observe the maximum speed of the motor!

-

f

dmin

is only effective:

- With analog setpoint input.
- With the motor potentiometer function ”DOWN”.

Special features

fd

C011
(fdmax)

C010
(fdmin)

0 %

100 %