7.5.10.3 Frequency precontrol

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C238

¤ Frequency

precontrol

-1-

-0-

No precontrol

-1-

With setpoint precontrol

Function

C238 = -1-

-

The process controller has only limited influence on the process.

The following setpoint precontrol is possible:
A The setpoint of the process controller is derived from the precontrol value (C181 = 0).

- Applications with frequency precontrol are e.g. speed controls.

B The setpoint of the process controller is selected under C181 (C181

 0).

- Applications are e.g. dancer controls, pressure and flow-rate controls

7.5.10.4 Frequency setting range

Code

Name

Possible settings

IMPORTANT

Code

Name

Lenze

Choice

Info

IMPORTANT

C239

¤ Frequency setting

range

-0-

-0-

Bipolar

-1-

Unipolar

Function

C239 = -0-

-

Allows both directions of rotations for the control process.

C239 = -1-

-

Allows only one direction of rotation for the control process.

Application with frequency setting range are, for instance:

-

Fan controls

-

Dancer controls

Important

Only if C005 > -0-, C239 has an influence.