Technical data – Lenze 8200 Frequency inverters User Manual

Page 43

Advertising
background image

Technical Data

8200SHB0199

3-11

150 % overload

Type

8221

8222

8223

8224

Order No.

EVF8221-E

EVF8222-E

EVF8223-E

EVF8224-E

Variant ”Cold Plate”

Type

8221-V003

8222-V003

Order No.

EVF8221-C-V003 EVF8222-C-V003

Variant “HVAC”

Type

8221-V020

8222-V020

8223-V020

8224-V020

Order No.

EVF8221-E-V020 EVF8222-E-V020 EVF8223-E-V020 EVF8224-E-V020

Power derating

[%/K]

[%/m]

40

•C < T

V

< 50

•C: 2.5 %/K

1000 m a.m.s.l.

h $ 4000 m a.m.s.l.: 5 %/1000 m

Field
frequency

Resolution

Absolute

0.02 Hz

Field
frequency Digital setpoint selection

Accuracy

á0.05 Hz

Analog setpoint selection

Linearity

á0.5 %(max. selected signal level: 5 V or 10 V)

Analog setpoint selection

Temperature
sensitivity

0

¡ 40 •C: +0.4 %

Offset

á0 %

Weight
”Cold Plate” without heat sink

m [kg]

15
11

15
11

15

-

33.5

-

Printed in bold

Data for the operation with factory setting and a chopper frequency of 8 kHz.

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I

rx

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

4)

Only with variant “HVAC”

5)

Must only be operated with C144 = -1- (automatic chopper frequency derating at

J

max

= + 5

•C). Ensure not to

exceed the currents.

*

Chopper frequency of the inverter

Show/Hide Bookmarks

Advertising