Preface and general information – Lenze 8200 Frequency inverters User Manual

Page 26

Advertising
background image

Preface and general information

8200SHB0199

1-10

Considered basic standards for the test of noise emission:

Basic standard

Test

Limit value

EN 55022 7/92

Radio interference housing and mains
Frequency range 0.15 - 1000 MHz

Class B
for use in residential areas
and commercial premises

EN 55011 7/92
(used in addition to the
requirements of IEC 22G)

Radio interference housing and mains
Frequency range 0.15 - 1000 MHz
The emission of noise in industrial premises is not
limited in IEC 22G.

Class A
for use in
industrial premesis

IEC 801-2 /91

Electrostatic discharge
on housing and heat sink

Severity 3
6 kV with contact discharge
8 kV air discharge

IEC 1000-4-3

Electromagnetic fields
Frequency range 26 - 1000 MHz

Severity 3
10 V/m

ENV 50140 /93

High-frequency field
Frequency range 80 - 1000 MHz,
80 % amplitude modulated

Severity 3
10 V/m

Fixed frequency
900 MHz with 200 Hz, 100 % modulated

10 V/m

IEC 801-4 /88

Fast transients
burst on power terminals

Severity 3
2 kV / 5 kHz

Burst on bus and control cables

Severity 4
2 kV / 5 kHz

IEC 801-5

Surge test
Mains cables

Installation class 3

Hameln, 01 October, 1995

________________

(i. V. Loy)
Product Manager