Application examples

8200SHB0199

15-10

Code settings for unit 2:

Code

Name

Possible settings

Code

Name

Lenze

Choice

Info

C001 Operating mode

-0-

-0-

Setpoint selection via term. 8 (jumper setting
see chapter 4.2.8.2)
Control via terminals parameter setting with
8201BB

C005 Configuration

-0-

-0-

Operation with open-loop control via
terminal 8

C014 Control mode

-0-

-3-

Square characteristic V

f

d

2

with constant

V

min

boost

According to the information given in both tables (code setting for unit 1 and 2):

1. All other parameters are based on the factory setting.

2. Set the rated motor data under C088 (rated motor current) and C091 (motor cos

Ö) depending on the motor

connected.