4 rated data (operation with 150 %overload), 1 types 8201 to 8204, Rated data (operation with 150 % overload) – Lenze 8200 Frequency inverters User Manual

Page 37: Types 8201 to 8204, Technical data, 4 rated data

Advertising
background image

Technical Data

8200SHB0199

3-5

3.4

Rated data

(Operation with 150 % overload)

3.4.1

Types 8201 to 8204

150 % overload

Type

8201

8202

8203

8204

Order No.

EVF8201-E

EVF8202-E

EVF8203-E

EVF8204-E

Variant ”reduced assembly
depth”

Type

8202-V002

Variant ”reduced assembly
depth”

Order No.

EVF8202-E- V002

Mains voltage

V

r

[V]

190 V -0 %

$ V

r

$ 260 V +0 %; 45 Hz ¡ 65 Hz á0%

Alternative DC supply

V

DC

[V]

270 V -0 %

$ V

DC

$ 360 V +0 %

Mains current

4)

with mains filter/mains choke
without mains filter/mains choke

I

mains

[A]

4.2
5.0

7.5
9.0

12.5
15.0

17.0

-

Data for mains operation with 1 AC / 230 V / 50 Hz/60 Hz; 270 V

$ V

DC

$ 275 V

Motor power (4 pole ASM)
at 9.2 kHz*

P

r

[kW]

0.37

0.75

1.5

2.2

Motor power (4 pole ASM)
at 9.2 kHz*

P

r

[hp]

0.5

1.0

2.0

2.9

Output power U, V, W at 9.2 kHz*

S

r9.2

[kVA]

1.0

1.5

2.7

3.6

Output power + U

G

, -U

G

1)

P

DC

[kW]

0.0

0.0

0.0

0.0

Output current

I

r

[A]

2.6

4.0

7.0

9.5

Max. output current for 60 s

2)

I

rmax

[A]

3.9

6.0

10.5

14.2

Motor voltage

3)

V

M

[V]

0 - 3 x V

mains

/ 0 Hz

¡ 50 Hz, if required up to 240 Hz

Power loss (operation with I

r

)

P

loss

[W]

30

50

70

100

Power derating

[%/K]

[%/m]

40

•C < T

V

< 50

•C: 2.5 %/K

1000 m a.m.s.l.

h $ 4000 m a.m.s.l.: 5 %/1000 m

Field
frequency

Resolution

Absolute

0.05 Hz

Field
frequency

Digital setpoint
selection

Accuracy

á0.05 Hz

Analog setpoint
selection

Linearity

á0.5 %(max. selected signal level, 5 V or 10 V)

Analog setpoint
selection

Temperature
sensitivity

0

¡ 40 •C: +0.4 %

Offset

á0.3 %

Weight

m [kg]

1.0

1.3

Variant 1.0

2.2

2.2

1)

This power can be additionally obtained when operating a matching motor

2)

The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I

r

.

3)

With mains choke/mains filter: max. output voltage = approx. 96 % of the mains voltage

4)

Observe the N-conduction load when having a symmetrical mains distribution! (See electrical installation)

*

Chopper frequency of the inverter

Show/Hide Bookmarks

Advertising