2 selection example for 4 drives, 1 supply only via controllers, Selection example for 4 drives – Lenze 8200 Frequency inverters User Manual

Page 255: Supply only via controllers, Network of several drives

Advertising
background image

Network of several drives

8200SHB0199

10-12

10.3.2

Selection example for 4 drives

10.3.2.1 Supply only via controllers

Drive data

Drive

Controller type

Motor P

M

Efficiency

Drive 1

9328

22 kW

Drive 2

9325

5.5 kW

h = 0.9

Drive 3

8214

3.0 kW

h = 0.9

Drive 4

8212

1.5 kW

1. Determine DC-power requirements:

- Power loss P

loss

TAB 1.

3

'&



L 

Æ

3

0L

®

3

9L

É

3

'&

 N:



 N:

 N:



 N:

 N:





 N:





3

'&

 N:

2. Determine first input:

- P

DC100%

TAB 1.

9328

9325

8214

8212

P

DC100%

32.7 kW

7.2 kW

4.1 kW

2.0 kW

- First input selected is 9328.

- Additionally required input powers are:

34.573 kW - 32.7 kW = 1.875 kW

3. Determine the second input:

- Input power for 9325/8214/8212 from ”9328/8222” in TAB 1.

9325

8214

8212

P

DC2

5.4 kW

3.2 kW

not possible

- The power of 8214 is not sufficient.

4. Result:

- This drive network must be connected to the three-phase AC mains via

the controllers 9328 and 8214.