5 skip frequencies, Skip frequencies, Configuration – Lenze 8200 Frequency inverters User Manual

Page 170: Only “hvac” controllers

Advertising
background image

Configuration

8200SHB0199

7-33

7.5.9.5

Skip frequencies

Only “HVAC” controllers

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C625* Skip frequency 1

480.00 0.00

{0.02 Hz}

480.00

C626* Skip frequency 2

480.00 0.00

{0.02 Hz}

480.00

C627* Skip frequency 3

480.00 0.00

{0.02 Hz}

480.00

C628 Bandwidth of skip

frequencies

0.00

0.00

{0.01 %}

100.00

Function

With certain output frequencies, mechanical resonances might occur in the drive (e.g. fan). The skip
frequencies eliminate these unwanted output frequencies. The bandwidth (

af) determines the

range of skip frequencies.
With skip frequency = 480.00 Hz, the function is not active.
The function is within the frequency setpoint range of the ramp function generator.

Adjustment

-

Set the required skip frequencies under C625, C626, C627.

-

C628 defines the bandwidth of skip frequencies.
- Calculate the bandwidth (

Df) for the corresponding skip frequency:

of [Hz] Skip frequency [Hz] ô

C628 [%]

100 %

Important

-

The skip frequencies are only effective in the main setpoint channel (see signal flow chart).

-

C625, C626, C627, C628 are only stored in parameter set 1.

f

skip1

f

skip3

f

skip2

C625

C626

C627

C628

C628

C628

fd

set1

fd

set2

f

f

f

FIG 7-3

Skip frequencies and their bandwidth (

a

f)

Show/Hide Bookmarks