Configuration

8200SHB0199

7-91

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Choice

Lenze

Name

C111

¤ Monitor signal

-0-

-0-

Field frequency

-1-

Unit load

-2-

Motor current

-3-

DC-bus voltage

-4-

Motor power

-5-

Motor voltage

-6-

Analog output 1/f

d

(1/C050)

-7-

Field frequency of
f

dmin

(C010) ... f

dmax

(C011)

-8-

Actual PID controller value

Page 7-69

Selection -9- ... -25-
corresponds to the
relay output functions
C008 and C117:

-

LOW = 0 V

-

HIGH = 10 V

-9-

Ready for operation

-10-

TRIP fault message

-11-

Motor is running

-12-

Motor is running / CW rotation

-13-

Motor is running / CCW rotation

-14-

Field frequency f

d

= 0

-15-

f

dset

reached

-16-

Q

min

reached

-17-

I

max

reached

-18-

Overtemperature (

Ô

max

-10

•)

-19-

TRIP, Q

min

or IMP set

822X/824X

-20-

PTC warning

-21-

Apparent motor current
(C054) < current threshold (C156)

-22-

Apparent motor current
(C054) < current threshold (C156)
and f

d

> Q

min

threshold

-23-

Apparent motor current
(C054) < threshold (C156) and
input of ramp function generator =
output of ramp function generator

822X/824X

-24-

Warning motor phase failure

-25-

f

d

(C050) < f

dmin

(C010)

C114

¤ Signal level digital

inputs

-0-

E4

E3

E2

E1

-0-

0

0

0

0

-1-

0

0

0

1

-2-

0

0

1

0

-3-

0

0

1

1

-4-

0

1

0

0

-5-

0

1

0

1

-6-

0

1

1

0

-7-

0

1

1

1

-8-

1

0

0

0

-9-

1

0

0

1

-10-

1

0

1

0

-11-

1

0

1

1

-12-

1

1

0

0

-13-

1

1

0

1

-14-

1

1

1

0

-15-

1

1

1

1

Page 7-52

0: Ex is not inverted
1: Ex is inverted