3 setpoint input via jog frequencies, Setpoint input via jog frequencies, Configuration – Lenze 8200 Frequency inverters User Manual

Page 180

Advertising
background image

Configuration

8200SHB0199

7-43

7.5.11.3 Setpoint input via JOG frequencies

Code

Name

Possible settings

IMPORTANT

Lenze Choice

Info

C037 JOG value 1

20.00 0.00

{0.02 Hz}

480.00

-480.00

{0.02 Hz}

480.00 HVAC only

C038 JOG value 2

30.00 0.00

{0.02 Hz}

480.00

-480.00

{0.02 Hz}

480.00 HVAC only

C039 JOG value 3

40.00 0.00

{0.02 Hz}

480.00

-480.00

{0.02 Hz}

480.00 HVAC only

Function

The setpoint input via JOG frequencies is only active, if C007 is set accordingly
(series “Standard”: see chapter 7.8, “Code table”; series “HVAC”: see chapter 7.9, ”Code table”).

Activate

-

JOG value 1 via control terminal E1 or

-

binary coded up to three JOG frequencies via the control terminals E1 and E2.

Activation
Series “Standard”:

-

C007 = -3-, -4-, -5-, -6-, -9-, -14-, -15-, -20-, -22-:

Function

E1

Other setpoint source

LOW

JOG 1 active

HIGH

-

C007 = -0-, -1-, -2-, -16-:

Function

E1

E2

Other setpoint source

LOW

LOW

JOG 1 active

HIGH

LOW

JOG 2 active

LOW

HIGH

JOG 3 active

HIGH

HIGH

Series “HVAC”:

-

C007 = -0-,

-6-, -9-, -14-, -15-, -16-, -20-, -22-, -28-, -29-,

-30-, -35-, -37-

-41-, -46-, -47-, -49-, -50:

Function

EX

Other setpoint source

LOW

JOG 1 active

HIGH

or

Function

E1 (E3)

E2 (E4)

Other setpoint source

LOW

LOW

JOG 1 active

HIGH

LOW

JOG 2 active

LOW

HIGH

JOG 3 active

HIGH

HIGH

Important

-

The setting of f

dmax

(C011) limits the field frequency also for JOG values.

-

The setting of f

dmin

(C010) is not effective for setpoint input by means of JOG values.

Special features

The display value of the parameter can be related to an application datum (C500, C501)
(see chapter 7.6.3).