Commissioning

8200SHB0199

5-10

5.4.2.2

Optimise V/f-characteristic control with auto boost
(C014 = -0-/ -1-)

821X/822X/824X setting range:

Function is not available

820X setting range:

Required codes

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C015 V/f-rated frequency

50.00

30.00

{0.05 Hz}

960.00

C016 V

min

setting

*

0.00

{0.02 %}

40.00

*depends on the unit

C021 Slip compensation

0.0

0.0

{0.1 %}

12.0

Setting sequence

1.If necessary, select V/f

characteristic with auto boost
(C014 = -0- or -1-).

2.Select V/f-rated frequency

(C015).

-

The V/f-rated frequency determines the slope of the V/f characteristic and has considerable
influence on the current, torque and power performance of the motor.

-

An internal mains voltage compensation compensates deviations in the mains during operation.
Therefore, they do not have to be considered for the setting of C015.

-

Use standard motors with 230/400 V with

a connection, since with an input voltage of 230 V a

max. of 3AC 230 V is at the output.

Adjustment
Calculate the frequency to be set under C015:

C015 [Hz]

230 V

V

rmotor

[V]

ô f

dr

[Hz]

V

rmotor

Rated voltage to motor nameplate [V]
Observe the connection mode (e.g. with a
motor voltage to nameplate 230/400 V /

D

V

rmotor

= 230 V AC.

f

dr

Rated frequency to motor nameplate [Hz]

C014 = -0-
Linear characteristic

C014 = -1-
Square characteristic (e.g. for pumps, fans)

o u t
r m o t o r

V

V

1

V

m i n

0

0

1

C 0 1 5

f

d r m o t o r

o u t
r m o t o r

V

V

V

m i n

0

0

1

C 0 1 5

f

d r m o t o r

K 3 5 . 0 0 6 6 G B