Network of several drives – Lenze 8200 Frequency inverters User Manual

Page 248

Advertising
background image

Network of several drives

8200SHB0199

10-5

-

Use the assigned DC-bus fuses F4, F5.
(For protection, see chapter 10.2.5).
The controller is protected by the two-pole, type-dependent protection of
the controller and the DC-bus against:

- internal short circuit,

- internal earth fault,

- a short circuit +U

G



-U

G

on the DC-bus,

- an earth fault via +U

G



PE or -U

G



PE.

Note!

-

With only two controllers connected to the network, one fuse pair F4/F5 is
sufficient.

- The rating must be made taking into account the weakest controller.

-

Connect an additional fuse pair F4/F5 before each controller, if more than
two controllers are connected to the DC-bus.