Configuration – Lenze 8200 Frequency inverters User Manual

Page 216

Advertising
background image

Configuration

8200SHB0199

7-79

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Choice

Lenze

Name

C013 Deceleration time T

if

Page 7-16,

7-55

820X

5.00

0.00

{0.05 s}

999.00

821X/822X/

824X

5.00

0.00

{0.02 s}

999.00

C014

¤ Control mode

Page 7-19,

7-22, 7-24

820X

-0-

-0-

Linear characteristic V

f

d

with

auto boost

-1-

Square characteristic V

f

d

2

with

auto boost

-2-

Linear characteristic V

f

d

with

constant V

min

boost

-3-

Square characteristic V

f

d

2

with

constant V

min

boost

821X/822X/

824X

-4-

-4-

Motor-current control

C015 V/f-rated frequency

Page 7-22

C015

820X

50.00

30.00

{0.05 Hz}

960.00

821X/822X/

824X

50.00

7.50

{0.02 Hz}

960.00

C016 V

min

setting

Page 7-24

C016

820X

*

0.00

{0.02 %}

40.00

*depends on the unit

821X/822X/

824X

0.00

0.00

{0.02 %}

40.00

C017

œ Threshold Q

min

0.00

0.00

{0.02 Hz}

480.00 Page 7-65

C018

¤ Chopper frequency

Page 7-29

C018

¤

821X/822X/824X

-1-

-0-

4 kHz power-loss optimised

-1-

8 kHz power-loss optimised

-2-

12 kHz power-loss optimised

-3-

16 kHz power-loss optimised

-4-

12 kHz noise optimised

-5-

16 kHz noise optimised

C019

œ Threshold

auto DC brake

Page 7-56

821X/822X/824X

0.10

0.10

{0.02 Hz}

5.00

C021 Slip compensation

Page 7-28

* If C014 = -2-, -3-,

controller dependent

820X

0.0*

0.0

{0.1 %}

12.0

821X/822X/

824X

0.0*

0.0

{0.1 %}

20.0

C022 I

max

limit

(motor mode)

150

30

{1 %}

150 Page 7-17

C023 I

max

limit

(generator mode)

80

30

{1 %}

110 Page 7-17

The current-limit
controller for operation
in generator mode is

822X/824X

80

30

{1 %}

150 As of software

1.6

controller for operation
in generator mode is
not active at 30 %.

C034

¤ Master current

-0-

-0-

0 to 20 mA /
0 to 5 V / 0 to 10 V

-1-

4 to 20 mA

Page 7-40

Show/Hide Bookmarks

Advertising