Configuration – Lenze 8200 Frequency inverters User Manual

Page 231

Advertising
background image

Configuration

8200SHB0199

7-94

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Choice

Lenze

Name

C182* Integration time

ramp function
generator S-shape

0.00

0.00

{0.01 s}

50.00 Page 7-32

-

C182 = 0.00
- Linear ramp

function generator

-

C182 > 0.00
- Ramp function

generator S shape
with
T

i

time = C182

C196*

¤ Input condition

autom. DC injection
brake

-0-

-0-

DC brake active at C050 < C019

-1-

DC brake active at C050 < C019
and Setpoint < C019

Page 7-56

C200 Software EKZ

C238

¤ Frequency

precontrol

-1-

-0-

No precontrol

-1-

With setpoint precontrol

Page 7-34,

7-39

C239

¤ Frequency setting

range

-0-

-0-

Bipolar

-1-

Unipolar

Page 7-39

C304 Password1

C305 Password2

C307 Contents of the

address

Should only be
changed by the

C308 Address

changed by the
Lenze Service!

C377*

¤ Gain voltage

detection

822X/824X

Lenze Service!

C395 LWORD process

input data

Only for bus operation

C396 LWORD process

output data

Only for bus operation

C425

¤* Adjustment of digital

frequency

-2-

Dig.-

Reso-

Scann-

Max.-

freq.

lution

ing

freq.

-0-

100 Hz 1/200

1 s

300 Hz

-1-

1 kHz

1/200

100 ms

3 kHz

-2-

10 kHz 1/200

10 ms

10 kHz

-3-

10 kHz 1/1000

50 ms

10 kHz

-4-

10 kHz 1/10000 500 ms 10 kHz

Page 7-60

When using the
analog input module
9279 for the
frequency input E1:

-

Set C425 to 2, 3
or 4

C426* Gain adjustment

frequency input E1

100

-200.0

{0.1 %}

200.0 Page 7-60

C427 Offset adjustment

frequency input E1

0.0

-12.5

{0.1 %}

12.5 Page 7-60

C500* Display factor

Application datum

2000

1

{1}

25000 Page 7-63

Application datum
numerator

C501* Display factor for

process variable

10

1

{1}

25000 Page 7-63

process variable
denominator

C597*

¤ Activation of motor

phase failure
detection

Page 7-73

822X/824X

-0-

-0-

Inactive

-1-

TRIP

-2-

Warning

Show/Hide Bookmarks