Configuration

8200SHB0199

7-92

Code

IMPORTANT

Possible settings

Name

Code

IMPORTANT

Info

Choice

Lenze

Name

C115

¤ Priority mask digital

inputs

-0-

E4

E3

E2

E1

-0-

0

0

0

0

-1-

0

0

0

1

-2-

0

0

1

0

-3-

0

0

1

1

-4-

0

1

0

0

-5-

0

1

0

1

-6-

0

1

1

0

-7-

0

1

1

1

-8-

1

0

0

0

-9-

1

0

0

1

-10-

1

0

1

0

-11-

1

0

1

1

-12-

1

1

0

0

-13-

1

1

0

1

-14-

1

1

1

0

-15-

1

1

1

1

Page 7-53

0: Function Ex
depends on C001
1: Function Ex is
independent of C001

-

Ctrl. inhibit and TRIP
reset always have
first priority.

-

With -0- also TRIP
set and QSP have
priority.

C117

¤ Function relay K2

-0-

-0-

Ready for operation

-1-

TRIP fault message

-2-

Motor is running

-3-

Motor is running / CW rotation

-4-

Motor is running / CCW rotation

-5-

Field frequency f

d

= 0

-6-

f

dset

reached

-7-

Q

min

reached

-8-

I

max

reached

-9-

Overtemperature (

J

max

-10

•C)

-10-

TRIP or Q

min

or IMP

Page 7-65 ff

822X/824X

-11-

PTC warning

-12-

Apparent motor current
(C054) < threshold C156

-13-

Apparent motor current
(C054) < current threshold C156
and f

d

> Q

min

threshold (C017)

-14-

Apparent motor current
(C054) < threshold C156 and input
of ramp function generator =
output of ramp function generator

822X/824X

-15-

Warning motor phase failure

-16-

f

d

(C050) < f

dmin

(C010)

C119

¤ Function PTC

822X/824X

-0-

-0-

PTC input not active

-1-

PTC input active, TRIP and pulse
inhibit will be set

-2-

PTC input active
Warning

Page 7-72

C120 I

2

kt switch-off

Page 7-71

C120

822X/824X

0

0

{1 %}

100

If C120 = 0, the
function is not active