7 analog plug-in module 8279ib, 1 features, Analog plug-in module 8279ib – Lenze 8200 Frequency inverters User Manual

Page 56: Features, Technical data

Advertising
background image

Technical Data

8200SHB0199

3-24

3.7

Analog plug-in module 8279IB

Order No.

EMZ8279IB

Note!

Only controllers of the 8210, 8220 and 8240 HVAC (V020) series can be equipped
with an analog plug-in module 8278IB, because they provide the required
software.

3.7.1

Features

The analog plug-in module 8279IB provides a second analog input. It converts an
analog input signal (0 ... 10 V or 0 ... 20 mA) into a digital signal (pulse frequency
0 ... 10 kHz) with the following levels:

-

LOW level = 0 V ... 3 V

-

HIGH level = 12 V ... 30 V

For operation with 4 ... 20 mA, the following codes must be parameterised:

-

C426 = 125 %

-

C427 = -12.5 %

Further notes can be obtained from the code table.

Controllers of the 8210, 8220 and 8240 series equipped with an analog plug-in
module, can be used for the following process controller applications:

-

Pressure regulation

-

Temperature or volume control

-

Setpoint summation

-

Speed or dancer-position control

To operate the analog plug-in module, the terminal configuration C007 has to be
set to -28-...-45- or -48- ... -51-.

The inverters with plug-in module are subject to the technical data and application
conditions of the controllers.