Installation – Lenze 8200 Frequency inverters User Manual

Page 97

Advertising
background image

Installation

8200SHB0199

4-40

Terminal

Use
(Factory setting is printed in bold)

Level

Data

Analog
inputs

7

GND 1

Analog
inputs

8

Setpoint input,
reference:
Terminal 7
(0 to 10 V)

6

4

2

5

3

1

5 - 6
5 - 6
3 - 4
1 - 2

0 to 20 mA
4 to 20 mA
0 to 5 V
0 to 10 V

Resolution: 820X: 9 bit,
821X/822X/824X: 10 bit
Linearity fault:

–0.5 %

Temperature fault: 0.3 % (0 ... + 40

•C)

Input resistance
Voltage signal: > 100 k

Jumper

Input resistance
Voltage signal: > 100 k

ˆ

Current signal: 250

ˆ

9

Supply for setpoint potentiometer

5.2 V / 6 mA

Analog
output

62

Analog output, reference: Terminal 7
(Field frequency)

0 ... 6 V / 2 mA
0 ... 10 V / 2 mA

1)

Resolution: 820X: 8 bit
821X/822X/824X: 10 bit

Digital
inputs

20

Voltage supply for digital inputs
820X: 12 V / 20 mA
821X/822X/824X: 15 V / 20 mA

28

Controller enable

HIGH

HIGH:

12 V ... 30 V

LOW:

0 V ... 3 V

E4

CW/
CCW rotation (CW/CCW)

CW: LOW
CCW: HIGH

HIGH:

12 V ... 30 V

LOW:

0 V ... 3 V

E3

DC-injection brake

HIGH

E2

JOG frequencies
20 Hz, 30 Hz, 40 Hz

Binary code

E1

JOG frequencies
20 Hz, 30 Hz, 40 Hz

Binary code

39

GND 2 (reference for external voltages)

Monitoring T1

Motor-temperature monitoring
(PTC thermistor/thermal contact)

If not used: Set parameter C119 = -0-!

T2

Motor-temperature monitoring
(PTC thermistor/thermal contact)

Terminal

Use
(Factory setting is printed in bold)

Relay position (switched)

Data

Relay
output K1

K 11

Relay output normally-closed contact
(TRIP)

Opened

24 V AC / 3.0 A or
60 V DC / 0.5 A

output K1

K 22

Relay mid-position contact

60 V DC / 0.5 A

K 24

Relay output normally-open contact
(TRIP)

Closed

Relay
output K2

K 21

Relay output normally-closed contact
(Ready for operation)

Opened

250 V AC / 3.0 A or
60 V DC / 0.5 A

output K2

K 22

Relay mid-position contact

250 V AC / 3.0 A or
60 V DC / 0.5 A

K 24

Relay output normally-open contact
(Ready for operation)

Closed

250 V AC / 3.0 A or
60 V DC / 0.5 A

1)

With 821X/822X/824X HVAC (V020)

Show/Hide Bookmarks