Troubleshooting and fault elimination – Lenze 8200 Frequency inverters User Manual

Page 238

Advertising
background image

Troubleshooting and fault elimination

8200SHB0199

8-3

Display

Remedy

Cause

Fault

OC2

Earth fault

Grounded motor phase

Check motor; check cable

OC2

Earth fault

Excessive capacitive charging current of
the motor cable

Use motor cable which is shorter or has a lower
capacitance

OC3

Overload inverter during
acceleration or short circuit

Acceleration time too short (C012)

-

Increase acceleration time

-

Check drive selection

Defective motor cable

Check wiring

Interturn fault in the motor

Check motor

OC4

Overload controller during
deceleration

Deceleration time too short (C013)

-

Increase deceleration time

-

Check the selection of the brake resistor or
connect the brake chopper

OC5

I x t overload

Frequent and too long acceleration
processes with overcurrent

Check drive selection

Permanent overload with
I

motor

> 1.05 x I

rx

OC6

Overload motor

Motor is thermally overloaded, for
instance, because of

-

impermissible continuous current

-

Check drive selection

-

frequent or too long acceleration
processes

-

Check the setting under C120

OH

Heat sink temperature is
higher than the value set in
the controller

Ambient temperature
T

amb

> + 40

•C or +50 •C

-

Allow controller to cool and ensure ventilation

-

Check the ambient temperature in the control
cabinet

Heat sink very dirty

Clean heat sink

Incorrect mounting position

Change mounting position

OH3

PTC monitoring

Motor too hot because of excessive
currents or frequent and too long
accelerations

Check drive selection

PTC not connected

Connect PTC or switch-off monitoring
(C0585 = 3)

OH4

Overtemperature unit

Inside unit too hot

-

Reduce controller load

-

Improve cooling

-

Check fan in the controller

OU

Overvoltage

Mains voltage too high

Check voltage supply

OU

Overvoltage

Feedback operation
Braking operation

-

Prolong deceleration times

-

For operation with brake choppers:
- Check the selection and connection of the

brake resistor

- Increase the deceleration times

Earth leakage on the motor side

Check motor cable and motor for earth fault
(disconnect motor from inverter)

OUE

Overvoltage

Mains overvoltage longer than 5 s

Check mains voltage

Pr

Faulty parameter transfer
via the operating module

PAR1 and PAR2 are defective

It is absolutely necessary to repeat the data

Pr1

Faulty PAR1 transfer via the
operating module

PAR1 is defective

It is absolutely necessary to repeat the data
transfer or load the factory setting before
enabling the controller.

Pr2

Faulty PAR2 transfer via the
operating module

PAR2 is defective

enabling the controller.

rSt

Faulty auto-TRIP reset

More than 8 fault messages in
10 minutes

Depends on the fault message