Central supply via 934x for 821x/822x/824x/93xx, Network of several drives, Stop – Lenze 8200 Frequency inverters User Manual
Page 258: 934x, Show/hide bookmarks
Network of several drives
8200SHB0199
10-15
10.4.2
Central supply via 934X for 821X/822X/824X/93XX
L1
L2
L3
F1...F3
934X
PE
+UG
-UG
Z1
K1
U
V
W
M
3~
PE
L1
L2
L3
PE
+UG
-UG
PE
U
V
W
M
3~
PE
L1
L2
L3
PE
+UG
-UG
PE
F4 F5
Z2
M
3~
L3
N
PE
L1
L2
K1
K1
Mot1
ϑ
ON
OFF
Mot2
ϑ
Mot1
Mot2
821X/ 822X
824X/ 93XX
821X/ 822X
824X/ 93XX
FIG 10-3
Principle diagram: Central supply for network operation of 821X/822X/824X/93XX
Z1
Mains filter/choke
Z2
Regenerative power supply
F1 ... F5
Fuses
K1
Main contactor
Stop!
The DC-bus voltage thresholds of the 93XX controller and the 934X supply unit
must be set to the same value.
Note!
Z2 is selected after balancing the power in the DC-bus. If the power supply of the
supply is not sufficient, a parallel supply can be installed via the mains input of a
controller (see Network of severval drives with decentral supply).