3 thermal motor monitoring, 1 i2 x t monitoring, Thermal motor monitoring – Lenze 8200 Frequency inverters User Manual

Page 208: I2 x t monitoring, Configuration, X t monitoring

Advertising
background image

Configuration

8200SHB0199

7-71

7.7.3

Thermal motor monitoring

7.7.3.1

I

2

x t monitoring

Code

Name

Possible settings

IMPORTANT

Lenze

Choice

Info

C120 I

2

k t switch-off

0

0

{1 %}

100

Function

With the I

2

¼ t monitoring, self-ventilated three-phase AC motors can be thermally monitored without

using sensors.

Adjustment

-

Enter an individual load limit for the motor connected.
- If this values is exceeded for a longer period of time, the controller will set the fault OC6 and

switch-off (see chart).

-

The current limits C022 and C023 only have an indirect influence on the I

2

¼ t calculation:

- The settings of C022 and C023 can make the operation with maximum controller load (C056)

impossible.

-

When selecting a drive which does not match (output current much higher than rated motor
current):
- Reduce C120 by the factor of the mismatch.

Example:
With C120 = 100 % and a load of C056 = 150 %, the controller switches off after 60 s when
reaching f

d

> 40 Hz, or earlier with f

d

< 40 Hz.

Important

-

The setting 0 % deactivates the function.

-

This monitoring does not provide full motor protection since the calculated motor temperature is
set to ”0” after every mains connection or disconnection. The connected motor can be
overheated, if
- it is already hot but still overloaded,
- the cooling-air stream is interrupted or the air is too hot.

-

Full motor protection can be achieved with a PTC thermistor in the motor.
- We recommend the general use of PTC monitoring systems for multi-motor drives.

-

To prevent motors with forced ventilation from starting too early, this function can be deactivated.

-

If load-adapted motors are to be monitored at a load of < 100 %, C120 must also be reduced
accordingly.

-

The operation of the controller with 120 % overload might lead to the activation of the I

2

k t

switch-off, because the setting of C120 > 100 % is not possible.
- Deactivate the I

2

k t switch-off for the operation of the controller at 120 %overload.