Yaskawa AC Drive P1000 Bypass Technical Manual User Manual

Page 100

Advertising
background image

n

b5-46: PID Setpoint Monitor Unit Selection

Sets the digital operator display units in U5-01 and U5-04 when b5-20 is set to 3.

No.

Name

Setting Range

Default

b5-46

PID Setpoint Monitor Unit Selection

0 to 15; 25

0

Setting 0: WC (Inch of Water)
Setting 1: PSI (Pounds per Square Inch)
Setting 2: GPM (Gallons per Minute)
Setting 3: F (Degrees Fahrenheit)
Setting 4: CFM (Cubic Feet per Minute)
Setting 5: CMH (Cubic Meters per Hour)
Setting 6: LPH (Liters per Hour)
Setting 7: LPS (Liters per Second)
Setting 8: Bar (Bar)
Setting 9: Pa (Pascal)
Setting 10: C (Degrees Celsius)
Setting 11: Mtr (Meters)
Setting 12: Ft (Feet)
Setting 13: LPN (Liters per Minute)
Setting 14: CMM (Cubic Meters per Minute)
Setting 15: “Hg (Inches of Mercury)
Setting 25: No unit

n

b5-47: PID Output Reverse Selection 2

Determines whether a negative PID output reverses the direction of drive operation. When the PID function is used to trim

the frequency reference (b5-01 = 3 or 4), this parameter has no effect and the PID output will not be limited

(same as b5-11 = 1).

No.

Name

Setting Range

Default

b5-47

PID Output Reverse Selection 2

0, 1

1

Setting 0: Reverse Disabled

Negative PID output will be limited to 0 and the drive output will be stopped.

Setting 1: Reverse Enabled

Negative PID output will cause the drive to run in the opposite direction.

n

Fine-Tuning PID

Follow the directions below to fine tune PID control parameters:

5.2 b: Application

100

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual