B.5 d: References

Reference parameters set the various frequency reference values during operation.

u

d1: Frequency Reference

No.

(Addr.

Hex)

Name

Description

Values

Page

d1-01

(280)

Frequency Reference 1

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00

Max.: 60.00

106

d1-02

(281)

Frequency Reference 2

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00

Max.: 60.00

106

d1-03

(282)

Frequency Reference 3

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00

Max.: 60.00

106

d1-04

(283)

Frequency Reference 4

Sets the frequency reference for the drive. Setting units are determined by

parameter o1-03.

Default: 0.00 Hz

Min.: 0.00

Max.: 60.00

106

u

d2: Frequency Upper/Lower Limits

No.

(Addr.

Hex.)

Name

Description

Setting

Page

d2-01

(289)

Frequency Reference Upper

Limit

Sets the frequency reference upper limit as a percentage of the maximum

output frequency.

Default: 100.0%

Min.: 0.0

Max.: 110.0

107

d2-02

(28A)

Frequency Reference Lower

Limit

Sets the frequency reference lower limit as a percentage of the maximum

output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

107

d2-03

(293)

Master Speed Reference

Lower Limit

Sets the lower limit for frequency references from analog inputs as a

percentage of the maximum output frequency.

Default: 0.0%

Min.: 0.0

Max.: 110.0

107

u

d3: Jump Frequency

No.

(Addr.

Hex)

Name

Description

Values

Page

d3-01

(294)

Jump Frequency 1

Eliminates problems with resonant vibration of the motor/machine by

avoiding continuous operation in predefined frequency ranges. The drive

accelerates and decelerates the motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

108

d3-02

(295)

Jump Frequency 2

Eliminates problems with resonant vibration of the motor/machine by

avoiding continuous operation in predefined frequency ranges. The drive

accelerates and decelerates the motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

108

d3-03

(296)

Jump Frequency 3

Eliminates problems with resonant vibration of the motor/machine by

avoiding continuous operation in predefined frequency ranges. The drive

accelerates and decelerates the motor through the prohibited frequency ranges.

Setting 0.0 disables this function.

Parameters must be set so that d3-01 ≥ d3-02 ≥ d3-03.

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

108

d3-04

(297)

Jump Frequency Width

Sets the dead-band width around each selected prohibited frequency reference

point.

Default: 1.0 Hz

Min.: 0.0

Max.: 20.0

108

B.5 d: References

YASKAWA SIEP YAIP1B 01A YASKAWA AC Drive – P1000 Bypass Technical Manual

243

B

Parameter List